Fire Safety

Fire Protection

Safety Operation Procedures - Fire Protection

 

Arkansas State University - Jonesboro
Effective Date: 03/06/2017
Policy Number: 05-41
Section: Safety Operating Procedures
Subject: Safety – Fire Protection
1.0 Purpose
This procedure is designed to mitigate the risk of loss of life and property resulting from
fire in University buildings, and to ensure occupant compliance with fire codes and
directives from University insurance carriers.
2.0 Definitions
2.1 Burn Ban – Burn bans are issued by the County Judge when fire danger is high
in a particular area due to dry and/or windy conditions. Check the Arkansas
Forestry Commission website for a current list of burn bans in the state:
https://www.arkfireinfo.org/.
2.2 Fire-Safe – A perimeter or immediate area within 35 to 50 feet of hot work or
open flames that has been cleared of additional fire hazards such as flammables
and combustibles, or otherwise protects flammables or combustibles that cannot
be moved with fire-resistant shielding
2.3 Fire-Rated – A surface such as a wall, floor or ceiling, or entire space, such as a
stairwell, that is designed to mitigate the spread of fire and smoke through
compartmentalization of the flames and to provide an Area of Rescue for people
with mobility impairment when elevators are inoperable due to fire alarm
activation.
2.4 Fire Watch – A dedicated team with no other responsibilities other than to watch
for fire in a building or sections of a building, and verify actual fires versus false
alarms to a dedicated person monitoring the fire panel when system components
must be offline. Dedicated fire watches are also required where hot work is being
performed within 35 feet and within 50 feet of permitted open fires outdoors.
2.5 Piggy-Backing – An informal industry term referring to the prohibited practice of
sequentially plugging power strips into additional power strips, which can result in
overloaded circuits and electrical fires.
2.6 Wind Advisory – As it relates to fire safety, a Wind Advisory often carries
increased risk of fire spreading outdoors. Check the National Weather Service in
Memphis for current and forecast wind conditions in Northeast Arkansas:
https://www.weather.gov/meg/. A Wind Advisory is issued when the following
conditions are expected:
a. Sustained winds of 31 to 39 mph for an hour or more
AND / OR
b. Wind gusts of 46 to 57 mph for any duration.
3.0 Restrictions on Open Flames
3.1 Storage of fireworks is prohibited in University buildings
3.2 Per Arkansas State Law, smoking is prohibited on all University property.
3.3 Fireworks displays on campus property require a permit from the Arkansas State
Fire Marshal with approval from University Police and Jonesboro Fire
departments.
a. Permits with the appropriate UPD and JFD signatures must be at the
Arkansas State Fire Marshal’s office in Little Rock for review no later than
five days prior to the fireworks display.
b. All events with fireworks must report the intention to use such displays on
the Campus Calendar Submit Event form, available online at:
https://www.astate.edu/calendar/submit-an-event.dot.
3.4 Indoor pyrotechnics or smoke effects are only allowed in First National Bank
Arena and Centennial Bank Stadium, and require a permit from the State Fire
Marshal with approval from University Police and Jonesboro Fire departments.
a. Permits with the appropriate UPD and JFD signatures must be at the
Arkansas State Fire Marshal’s office in Little Rock for review no later than
five days prior to the pyrotechnics display.
b. When a fire alarm system bypass is requested, a qualified fire watch must
be present at all times and be capable of:
i. Verifying an actual fire or false alarm originating at any point in the
building, then
ii. Fully activating the system within five minutes,
c. Venues must ensure that fire watch personnel are appropriately trained or
otherwise approved through University Safety & Emergency Management.
d. All events with pyrotechnics must report the intention to use such displays
on the Campus Calendar Submit Event form, available online at:
https://www.astate.edu/calendar/submit-an-event.dot.
3.5 Open flames in outdoor areas on University property, such as bonfires and open
fire pits, require approval from the Jonesboro Fire Department and notification to
University Police.
3.6 A written emergency action plan must be submitted to the University Safety &
Emergency Management five days prior to any outdoor event with open flames.
A template for the written emergency action plan is available online:
www.astate.edu/safety/emergency-management/controlled-fire-EAP.pdf.
a. Exceptions include fires in barbeque grills or other outdoor cookers that are
designed to contain and prevent the spread of flames or cooking fuel
(charcoal, wood, lighter fluid, or gases intended for cooking).
b. Open fires on University grounds must meet the following conditions as
prescribed by the University and City of Jonesboro Ordinance ORD-04.293:
i. Materials to be burned must consist of wood only
ii. Materials may be placed in a pile no larger than three feet in diameter
and two feet in height. (The annual Yell Like Hell bonfire held during
homecoming week is an exception to these size limitations, but requires
a fire pit to be dug by Facilities Management)
iii. Burning must be at least 50 feet from the nearest structure or vehicle
iv. Burning must be at least 25 feet from the nearest property line
v. Fire must be attended at all times
vi. Fire attendant(s) must have a charged hose and/or sufficient water
available to completely extinguish the fire in the event that it spreads
vii. Burning may not occur when a Wind Advisory or Burn Ban is issued for
Jonesboro or Craighead County
3.7 Open flames are prohibited in University buildings. Open flame devices and
materials include but are not limited to; candles, oil burning lamps and incense.
Exceptions include:

a. Laboratories where flames or burners are used with the proper safety
precautions in place.
b. Shops where hot work is performed in a fire-safe environment.
3.8 Any work involving flames or sparks outside of shops designated for such work
requires a Hot Work Permit.
a. The Hot Work Operating Procedure can be found online:
http://www.astate.edu/a/ehs/occupational-safety-health/files/hot-workproc.pdf
b. The hot work permit from can be found online:
https://arkansasstateuniversity.formstack.com/forms/hot_work_request.
4.0 Fire Protection Equipment
4.1 Vertical storage may not be stacked within 18 inches of sprinkler heads.
4.2 Tampering with or attempting to perform unauthorized maintenance on fire
suppression or detection systems is prohibited.
4.3 A three foot square of clear space around fire alarm pull stations and fire
extinguishers must be maintained. The clear space should extend three feet out
from the wall where the station/extinguisher is installed, and 1.5 feet along the
wall in each direction from the installed location.
4.4 Employees must not use fire extinguishers without prior knowledge of their
proper use.
a. Learn the basics of fire extinguisher use on the Safety & Emergency
Management website: http://www.astate.edu/a/ehs/emergencyservices/files/fire-safety.pdf
b. The Safety Office will determine the appropriate staff to receive hands-on
fire extinguisher training through job hazard analyses and the Community
Emergency Response Team (CERT) training
4.5 Any work that produces dust or other particles that may cause the fire alarm
system to activate requires prior notification to the University Police Department
and the Safety Office.
4.6 Failure to follow this procedure, render common practices or courtesies, or follow
rules of the road for the State of Arkansas could result in citation, disciplinary
action, and/or suspension of operator's SMV driving privileges.
5.0 Restrictions in Fire-Rated Spaces
5.1 Storage and displays in stairwells are strictly prohibited
5.2 Displays in egress areas must be installed in locations in such a way that a clear
and direct path to building exits is maintained at a width of at least five feet.
5.3 Storage is prohibited in emergency egress routes; including corridors, hallways
and lobbies that lead directly to building exits
a. Temporary storage in these spaces, such as chairs removed from rooms for
cleaning or tools required for a project, is permitted
b. Temporary storage must not be left unattended, and should be confined to
one side of an egress area in such a way that a clear and direct path to
building exits is maintained at a width of at least five feet.
5.4 Penetrations into fire-rated surfaces are prohibited unless fire-stopping systems
are in place. Fire-rated surfaces include, but are not limited to, concrete floors,
exposed/unfinished ceilings and stairwell walls.
5.5 Fire doors must remain closed at all times, unless equipped with an automatic
closing device designed to activate in a fire. Devices must meet applicable
Arkansas Fire Code requirements.
6.0 Electrical Fire Hazards
6.1 Storage of combustible material in electrical closets and mechanical rooms is
prohibited.
6.2 Use of extension cords as permanent wiring and permanent use of multi-plug
adapters are prohibited.
6.3 Surge protectors must be plugged directly into a wall outlet. Piggy-backing or
sequentially connecting surge protectors to additional surge protectors is
prohibited. Contact Facilities Management to request installation of additional
outlets.
6.4 Personal space heaters must be approved by Facilities Management. Contact
Facilities Management to procure an approved space heater through Central
Receiving.
6.5 Electrical panels must include knockouts or circuits blanks where circuits are not
in use.
6.6 A three foot square of clear space around electrical panels must be maintained.
a. Clearance extends three feet out from the wall where the panel is installed,
and 1.5 feet along the wall in each direction from the center of the panel.
b. If the panel is wider than three feet, the entire width of the panel will remain
clear, with three feet of clear space extending from the installed location,
and one foot along the wall in each direction where the sides of the panel
end

Hot Work Safety Program

Hot Work

Effective Date: 03/06/2017
Policy Number: 05-90
Section: Safety Operating Procedures
Subject: Safety – Hot Work
1.0 Purpose
This procedure is designed to mitigate or eliminate fire hazards associated with hot
work operations, such as welding, grinding or torch cutting.
2.0 Definitions
2.1 Fire-Safe – A perimeter or immediate area within 35 feet of hot work that has
been cleared of additional fire hazards such as flammables and combustibles, or
otherwise protects flammables or combustibles that cannot be moved with fireresistant shielding.
2.2 Fire Watch – A dedicated team with no other responsibilities other than to watch
for fire in a building or sections of a building, and verify actual fires versus false
alarms to a dedicated person monitoring the fire panel when system components
must be offline. Dedicated fire watches are also required where hot work is being
performed within 35 feet and within 50 feet of permitted open fires outdoors.
2.3 Hot Work – The following activities are considered Hot Work; welding, soldiering,
cutting, brazing, grinding, use of asphalt / tar kettle(s), or other work that might
create sufficient heat or spark, which could start a fire.
3.0 Scope
This program applies to all persons, including contractors, and Arkansas State
University units conducting Hot Work, as defined in the terms, on University owned or
leased property. NOTE: Areas permanently established and arranged to conduct
ongoing hot work are exempt.
3.1 Hot work shall not be conducted in any area other than those specifically
intended and designed for conducting said work unless the area has been
inspected and a Hot Work Permit (See section 4) has been issued to the
person(s) who will be conducting the actual work.
3.2 Only approved apparatus such as torches, regulators, pressure reducing valves,
acetylene generators, machines, manifolds, cables and hoses in good repair will
be used.
a. Manufacturer’s procedures/recommendations will be followed with respect to
the sequence of operations for welding, cutting and grinding equipment.
b. Only acetylene tanks that have been in the vertical position for a minimum of
2 hours will be used.
c. Torches will be pointed away from people and combustible materials when
lighting.
d. Torches will be lit with a friction lighter or stationary pilot flame. Torches will
not be lit from hot metal.
e. When equipment is not going to be used for periods of 30 minutes or more
or when left unattended the equipment will be shut off.
f. Only people who are trained and proficient will conduct hot work. Trainees
may perform work only when their trainer or supervisor is in the immediate
area.
3.3 A Hot Work Permit form will be completed prior to start of hot work. The Hot
Work Permit form can be found online: https://astate.campusoptics.com/pr/hotwork
By completing this form, employees performing hot work confirm and attest that
the following has been completed:
a. Inspections of the work site have been completed
b. The area is deemed fire safe and/or the necessary instructions to ensure
such safety is provided.
3.4 The online permit form will send an email to the submitter, the Work Order
Center and the Life Safety Systems Coordinator, including all safety precautions
to be taken and the designated work period timeframe.
a. Permits must be available at the work site. The email returned to the
submitter can be used for this purpose.
b. If the email is not available on the employee’s mobile device, arrangements
should be made with the Work Order Center, supervisor or other A-State
employee with access to a printer, in order to print and deliver the permit to
the work site.
3.5 If in the inspector’s opinion the area is not safe, work will postponed until such
time as the area is made safe.
3.6 In situations where delaying work to complete the form would allow, or increase
damage to University property or critical research project, the individual to
performing the hot work shall ensure the area is fire safe then proceed.
3.7 Open flames are prohibited in University buildings. Open flame devices and
materials include but are not limited to; candles, oil burning lamps and incense.
Exceptions include:
a. Laboratories where flames or burners are used with the proper safety
precautions in place.
b. Shops where hot work is performed in a fire-safe environment.
3.8 Permits for small projects and spot work will generally be issued for a period of
twelve hours only. However, in areas where the work will be ongoing for an
extended period of time, permits can be issued for periods not to exceed
seventy-two hours as long as the work or situational factors do not change.
3.9 Permits for closed construction sites with restricted public access can be issued
for the duration of the project, provided inspections are conducted to ensure the
area where hot work is performed is fire safe. Inspections must be documented
and records must be retained on the job site.
4.0 Fire Protection Equipment
4.1 Vertical storage may not be stacked within 18 inches of sprinkler heads.
4.2 Tampering with or attempting to perform unauthorized maintenance on fire
suppression or detection systems is prohibited.
4.3 A three foot square of clear space around fire alarm pull stations and fire
extinguishers must be maintained. The clear space should extend three feet out
from the wall where the station/extinguisher is installed, and 1.5 feet along the
wall in each direction from the installed location.
4.4 Employees must not use fire extinguishers without prior knowledge of their
proper use.
a. Learn the basics of fire extinguisher use on the Safety & Emergency
Management website: http://www.astate.edu/a/ehs/emergencyservices/files/fire-safety.pdf
b. The Safety Office will determine the appropriate staff to receive hands-on
fire extinguisher training through job hazard analyses and the Community
Emergency Response Team (CERT) training
4.5 Any work that produces dust or other particles that may cause the fire alarm
system to activate requires prior notification to the University Police Department
and the Safety Office.
4.6 Failure to follow this procedure, render common practices or courtesies, or follow
rules of the road for the State of Arkansas could result in citation, disciplinary
action, and/or suspension of operator's SMV driving privileges.
5.0 Restrictions in Fire-Rated Spaces
5.1 Storage and displays in stairwells are strictly prohibited
5.2 Displays in egress areas must be installed in locations in such a way that a clear
and direct path to building exits is maintained at a width of at least five feet.
5.3 Storage is prohibited in emergency egress routes; including corridors, hallways
and lobbies that lead directly to building exits
a. Temporary storage in these spaces, such as chairs removed from rooms for
cleaning or tools required for a project, is permitted
b. Temporary storage must not be left unattended, and should be confined to
one side of an egress area in such a way that a clear and direct path to
building exits is maintained at a width of at least five feet.
5.4 Penetrations into fire-rated surfaces are prohibited unless fire-stopping systems
are in place. Fire-rated surfaces include, but are not limited to, concrete floors,
exposed/unfinished ceilings and stairwell walls.
5.5 Fire doors must remain closed at all times, unless equipped with an automatic
closing device designed to activate in a fire. Devices must meet applicable
Arkansas Fire Code requirements.
6.0 Electrical Fire Hazards
6.1 Storage of combustible material in electrical closets and mechanical rooms is
prohibited.
6.2 Use of extension cords as permanent wiring and permanent use of multi-plug
adapters are prohibited.
6.3 Surge protectors must be plugged directly into a wall outlet. Piggy-backing or
sequentially connecting surge protectors to additional surge protectors is
prohibited. Contact Facilities Management to request installation of additional
outlets.
6.4 Personal space heaters must be approved by Facilities Management. Contact
Facilities Management to procure an approved space heater through Central
Receiving.
6.5 Electrical panels must include knockouts or circuits blanks where circuits are not
in use.
6.6 A three foot square of clear space around electrical panels must be maintained.
a. Clearance extends three feet out from the wall where the panel is installed,
and 1.5 feet along the wall in each direction from the center of the panel.
b. If the panel is wider than three feet, the entire width of the panel will remain
clear, with three feet of clear space extending from the installed location,
and one foot along the wall in each direction where the sides of the panel
end

Hot Work Permit

Hot Work PermitPermit Request • CampusOptics

Hot Work Precautions Checklist

Hot Work Precautions Checklist

Hot Work Precautions Checklist
Flame- or spark-producing equipment has been inspected and is in good repair
If fire suppression sprinklers are installed, they will remain operable for the duration of the hot work being
performed.
If any flammable dust, lint, vapors or liquids are present, they have been cleared from the hot work area.
If any combustible material that can be moved is present, it will be relocated at least 35 feet away from the hot
work area.
If any unpurged tanks or equipment previously containing flammable material are present, they have been
removed from the area.
If combustible floors, walls, materials or object that cannot be removed from the area are present, they will be
protected by fire resistant shielding or by wetting the area down. This includes grassy areas outdoors.
Ample fire extinguishing equipment is accessible and unobstructed within 15 feet of the hot work to be
performed.
A dedicated fire watch will be assigned to all areas within 35 feet of the hot work while the work is being
performed and for 30 minutes after the work has been completed, including floors below where necessary.
If cracks or floor openings are present within 35 feet of the hot work, the same precautions that apply to the
immediate area will apply to the floors below and a dedicated fire watch will be assigned to areas where sparks
may fall.
Hot work will be confined to the space deemed fire safe according to the checklist aboveFlame- or spark-producing equipment has been inspected and is in good repair
If fire suppression sprinklers are installed, they will remain operable for the duration of the hot work being
performed.
If any flammable dust, lint, vapors or liquids are present, they have been cleared from the hot work area.
If any combustible material that can be moved is present, it will be relocated at least 35 feet away from the hot
work area.
If any unpurged tanks or equipment previously containing flammable material are present, they have been
removed from the area.
If combustible floors, walls, materials or object that cannot be removed from the area are present, they will be
protected by fire resistant shielding or by wetting the area down. This includes grassy areas outdoors.
Ample fire extinguishing equipment is accessible and unobstructed within 15 feet of the hot work to be
performed.
A dedicated fire watch will be assigned to all areas within 35 feet of the hot work while the work is being
performed and for 30 minutes after the work has been completed, including floors below where necessary.
If cracks or floor openings are present within 35 feet of the hot work, the same precautions that apply to the
immediate area will apply to the floors below and a dedicated fire watch will be assigned to areas where sparks
may fall.
Hot work will be confined to the space deemed fire safe according to the checklist above

Fire protection

1.0 Purpose
This procedure is designed to mitigate the risk of loss of life and property resulting from
fire in University buildings, and to ensure occupant compliance with fire codes and
directives from University insurance carriers.
2.0 Definitions
2.1 Burn Ban – Burn bans are issued by the County Judge when fire danger is high
in a particular area due to dry and/or windy conditions. Check the Arkansas
Forestry Commission website for a current list of burn bans in the state:
https://www.arkfireinfo.org/.
2.2 Fire-Safe – A perimeter or immediate area within 35 to 50 feet of hot work or
open flames that has been cleared of additional fire hazards such as flammables
and combustibles, or otherwise protects flammables or combustibles that cannot
be moved with fire-resistant shielding
2.3 Fire-Rated – A surface such as a wall, floor or ceiling, or entire space, such as a
stairwell, that is designed to mitigate the spread of fire and smoke through
compartmentalization of the flames and to provide an Area of Rescue for people
with mobility impairment when elevators are inoperable due to fire alarm
activation.
2.4 Fire Watch – A dedicated team with no other responsibilities other than to watch
for fire in a building or sections of a building, and verify actual fires versus false
alarms to a dedicated person monitoring the fire panel when system components
must be offline. Dedicated fire watches are also required where hot work is being
performed within 35 feet and within 50 feet of permitted open fires outdoors.
2.5 Piggy-Backing – An informal industry term referring to the prohibited practice of
sequentially plugging power strips into additional power strips, which can result in
overloaded circuits and electrical fires.
2.6 Wind Advisory – As it relates to fire safety, a Wind Advisory often carries
increased risk of fire spreading outdoors. Check the National Weather Service in
Memphis for current and forecast wind conditions in Northeast Arkansas:
https://www.weather.gov/meg/. A Wind Advisory is issued when the following
conditions are expected:
a. Sustained winds of 31 to 39 mph for an hour or more
AND / OR
b. Wind gusts of 46 to 57 mph for any duration.
3.0 Restrictions on Open Flames
3.1 Storage of fireworks is prohibited in University buildings
3.2 Per Arkansas State Law, smoking is prohibited on all University property.
3.3 Fireworks displays on campus property require a permit from the Arkansas State
Fire Marshal with approval from University Police and Jonesboro Fire
departments.
a. Permits with the appropriate UPD and JFD signatures must be at the
Arkansas State Fire Marshal’s office in Little Rock for review no later than
five days prior to the fireworks display.
b. All events with fireworks must report the intention to use such displays on
the Campus Calendar Submit Event form, available online at:
https://www.astate.edu/calendar/submit-an-event.dot.
3.4 Indoor pyrotechnics or smoke effects are only allowed in First National Bank
Arena and Centennial Bank Stadium, and require a permit from the State Fire
Marshal with approval from University Police and Jonesboro Fire departments.
a. Permits with the appropriate UPD and JFD signatures must be at the
Arkansas State Fire Marshal’s office in Little Rock for review no later than
five days prior to the pyrotechnics display.
b. When a fire alarm system bypass is requested, a qualified fire watch must
be present at all times and be capable of:
i. Verifying an actual fire or false alarm originating at any point in the
building, then
ii. Fully activating the system within five minutes,
c. Venues must ensure that fire watch personnel are appropriately trained or
otherwise approved through University Safety & Emergency Management.
d. All events with pyrotechnics must report the intention to use such displays
on the Campus Calendar Submit Event form, available online at:
https://www.astate.edu/calendar/submit-an-event.dot.
3.5 Open flames in outdoor areas on University property, such as bonfires and open
fire pits, require approval from the Jonesboro Fire Department and notification to
University Police.
3.6 A written emergency action plan must be submitted to the University Safety &
Emergency Management five days prior to any outdoor event with open flames.
Contact the Office of Emergency Management for a template or to assist in writing a plan.

a. Exceptions include fires in barbeque grills or other outdoor cookers that are
designed to contain and prevent the spread of flames or cooking fuel
(charcoal, wood, lighter fluid, or gases intended for cooking).
b. Open fires on University grounds must meet the following conditions as
prescribed by the University and City of Jonesboro Ordinance ORD-04.293:
i. Materials to be burned must consist of wood only
ii. Materials may be placed in a pile no larger than three feet in diameter
and two feet in height. (The annual Yell Like Hell bonfire held during
homecoming week is an exception to these size limitations, but requires
a fire pit to be dug by Facilities Management)
iii. Burning must be at least 50 feet from the nearest structure or vehicle
iv. Burning must be at least 25 feet from the nearest property line
v. Fire must be attended at all times
vi. Fire attendant(s) must have a charged hose and/or sufficient water
available to completely extinguish the fire in the event that it spreads
vii. Burning may not occur when a Wind Advisory or Burn Ban is issued for
Jonesboro or Craighead County
3.7 Open flames are prohibited in University buildings. Open flame devices and
materials include but are not limited to; candles, oil burning lamps and incense.
Exceptions include:

a. Laboratories where flames or burners are used with the proper safety
precautions in place.
b. Shops where hot work is performed in a fire-safe environment.
3.8 Any work involving flames or sparks outside of shops designated for such work
requires a Hot Work Permit.
a. The Hot Work Operating Procedure can be found online:

b. The hot work permit from can be found online:
.
4.0 Fire Protection Equipment
4.1 Vertical storage may not be stacked within 18 inches of sprinkler heads.
4.2 Tampering with or attempting to perform unauthorized maintenance on fire
suppression or detection systems is prohibited.
4.3 A three foot square of clear space around fire alarm pull stations and fire
extinguishers must be maintained. The clear space should extend three feet out
from the wall where the station/extinguisher is installed, and 1.5 feet along the
wall in each direction from the installed location.
4.4 Employees must not use fire extinguishers without prior knowledge of their
proper use.
a. Learn the basics of fire extinguisher use in Taleo Learn. Search for Fire Extinguisher Safety, or contact EHS for in-person training.
b. The Safety Office will determine the appropriate staff to receive hands-on
fire extinguisher training through job hazard analyses and the Community
Emergency Response Team (CERT) training
4.5 Any work that produces dust or other particles that may cause the fire alarm
system to activate requires prior notification to the University Police Department
and the Safety Office.
4.6 Failure to follow this procedure, render common practices or courtesies, or follow
rules of the road for the State of Arkansas could result in citation, disciplinary
action, and/or suspension of operator's SMV driving privileges.
5.0 Restrictions in Fire-Rated Spaces
5.1 Storage and displays in stairwells are strictly prohibited
5.2 Displays in egress areas must be installed in locations in such a way that a clear
and direct path to building exits is maintained at a width of at least five feet.
5.3 Storage is prohibited in emergency egress routes; including corridors, hallways
and lobbies that lead directly to building exits
a. Temporary storage in these spaces, such as chairs removed from rooms for
cleaning or tools required for a project, is permitted
b. Temporary storage must not be left unattended, and should be confined to
one side of an egress area in such a way that a clear and direct path to
building exits is maintained at a width of at least five feet.
5.4 Penetrations into fire-rated surfaces are prohibited unless fire-stopping systems
are in place. Fire-rated surfaces include, but are not limited to, concrete floors,
exposed/unfinished ceilings and stairwell walls.
5.5 Fire doors must remain closed at all times, unless equipped with an automatic
closing device designed to activate in a fire. Devices must meet applicable
Arkansas Fire Code requirements.
6.0 Electrical Fire Hazards
6.1 Storage of combustible material in electrical closets and mechanical rooms is
prohibited.
6.2 Use of extension cords as permanent wiring and permanent use of multi-plug
adapters are prohibited.
6.3 Surge protectors must be plugged directly into a wall outlet. Piggy-backing or
sequentially connecting surge protectors to additional surge protectors is
prohibited. Contact Facilities Management to request installation of additional
outlets.
6.4 Personal space heaters must be approved by Facilities Management. Contact
Facilities Management to procure an approved space heater through Central
Receiving.
6.5 Electrical panels must include knockouts or circuits blanks where circuits are not
in use.
6.6 A three foot square of clear space around electrical panels must be maintained.
a. Clearance extends three feet out from the wall where the panel is installed,
and 1.5 feet along the wall in each direction from the center of the panel.
b. If the panel is wider than three feet, the entire width of the panel will remain
clear, with three feet of clear space extending from the installed location,
and one foot along the wall in each direction where the sides of the panel
end